SHEAR

Two 5 foot lengths of randomly selected hubless cast iron soil pipe were joined with an MG COUPLING, torqued to 175 inch-pounds, and the ends of the assembly were sealed with test plugs. One pipe was rigidly supported while the other was supported by a single block near the end of the pipe. The assemble was filled with water and the hydrostatic pressure held at 10 psi for the duration of the test. A load of 50 pounds per inch of nominal diameter of the pipe was uniformly applied over a arc of 120 degrees and along a longitudinal distance of 12 inches at the unsupported end of the pipe immediately adjacent to the coupling and held for 1 hour. Test required no leakage.  
MG COUPLING (sizes tested) Shear (pounds) Results
2" 100 No Leakage Occurred
3" 150 No Leakage Occurred
4" 200 No Leakage Occurred
5" 250 No Leakage Occurred
6" 300 No Leakage Occurred
8" 400 No Leakage Occurred
10" 500 No Leakage Occurred